Cable sizing

Cable Sizing Calculator

IEC 60364-5-52 cable sizing for AC and DC circuits: ampacity by installation method with ambient and grouping derating, the voltage-drop limit, and an optional short-circuit withstand check — with regional defaults for KSA, UAE, Egypt and the IEC baseline.

Report details for the PDF
Selected cable size
4 mm²
Cu / XLPE · method C · Three-phase AC
Voltage drop
3.44%
13.8 V vs 5.0% limit
69 % of the 5.0 % limit
Design current
32.1 A
20 kW @ 400 V × PF 0.9
Derating Ca × Cg
100%
Ca 1.00 (30 °C) × Cg 1.00 (1 circuit)
Derated ampacity
42 A
Base 42 A (method C) × derating
Short-circuit withstand
Not checked
Enter fault kA + disconnection time

Why this size, not the next one down

4 mm² is the smallest standard size where derated ampacity (42 A) exceeds the design current (32.1 A), voltage drop (3.44%) stays within the 5.0% limit. One size down fails on ampacity — that is the constraint that set the size. Reactance is ignored — the cable is small enough that resistance dominates the voltage drop.

Keep the sizing with the unit it was done for.

Power Stack gives every installed UPS a record — kVA, install date, notes and service history — so the cable size you just calculated is filed with the unit, and the next quote starts from what's on site.

Start free

The constraints that decide cable size

Cable sizing per IEC 60364-5-52 is a multi-constraint problem. The cable must be large enough to carry the design current without overheating its insulation, large enough that the voltage drop across its length stays within the regulated maximum, and — where the fault level is known — large enough to survive a short circuit until the protective device clears it. Most spreadsheet calculators handle one of the three. Picking the largest of the answers is the only correct result, and which constraint bites depends on the run length, the power factor, how aggressively the site has been derated, and how stiff the supply is.

Ampacity by installation method, then derated

IEC 60364-5-52 tabulates current-carrying capacity per reference installation method, because the same conductor sheds heat very differently in a thermally insulated wall (A1 / A2), in surface conduit or trunking (B1 / B2) and clipped direct to a wall or tray (C). A 16 mm² XLPE copper cable is good for 100 A clipped direct but only 73 A buried in an insulated partition. Two corrections then derate the table figure: Ca for ambient temperature (hot sites cut it sharply — at 50 °C, PVC is at 71% of its 30 °C rating) and Cg for grouping (touching cables derate each other — 3 circuits cut ampacity to 70%, 6 circuits to 57%). For aluminium, multiply the copper ampacity by 0.78.

Voltage drop: the second constraint

Voltage drop scales linearly with cable length and current, and inversely with cross-section. For cables under 25 mm², resistance dominates and the simplified formula Vd = k × ρ × L × I × cos φ / S gives the right answer. Above 25 mm² (and above 16 mm² when power factor drops below 0.9), reactance becomes a meaningful share of the total and the formula expands to include the X sin φ term. National codes set the limits: 5% from origin to load is the IEC baseline, 2.5% for DEWA final circuits, 3% is common practice for sub-mains and feeders.

DC circuits

Battery-string and DC-bus cables are the UPS dealer's most common sizing job and the most often done wrong. There is no power factor and no reactance: the current is simply I = P / V, and because a 48 V or 240 V DC bus carries far more current for the same power than a 400 V AC feed, voltage drop bites early — Vd = 2 × ρ × L × I / S across the go and return conductors. Ampacity uses the two-loaded-conductor column. Remember that a DC fault has no current zero to help the fuse clear it; check the string fuse's DC rating and let-through as well as the cable.

Short-circuit withstand (adiabatic check)

During a fault the conductor has no time to shed heat, so all the energy I² t goes into warming the copper. IEC 60364-4-43 §434.5.2 gives the minimum cross-section as S ≥ √(I² t) / k, where k depends on the conductor and the insulation's short-circuit temperature limit: 115 for copper / PVC, 143 for copper / XLPE, 76 and 94 for aluminium. Enter the prospective fault current at the cable and the protective device's disconnection time from its curve; if the thermal floor is above the ampacity answer, the calculator steps the size up and says so. A current-limiting MCCB or fuse with a short clearing time is often cheaper than the larger cable.

Why the regional defaults matter

Indoor ambient in a chilled office in northern Europe is 20–25 °C; outdoor in summer in the Gulf is 45–50 °C. Sizing the same load for both sites gives different answers — and a cable that's ampacity-correct in a temperate site can be one or two size steps short when installed in a hot region. The region defaults in this calculator preset Ca and the voltage- drop limit to the typical values for KSA, UAE, and Egypt, and fall back to a generic IEC baseline (30 °C ambient, 5% drop limit) for everywhere else. Override the defaults whenever your site differs.

Standards behind the math

Ampacity values from IEC 60364-5-52 Ed. 3.1 (2024-11) Tables B.52.4 (PVC) and B.52.5 (XLPE), copper, reference methods A1, A2, B1, B2 and C. Free-air methods E / F / G and buried methods D1 / D2 are not included — their ratings depend on spacing, arrangement and soil resistivity. Aluminium ampacity is the IEC convention of 0.78 × copper. Ca from Table B.52.14; Cg from Table B.52.17 (touching, single layer). Resistivity from IEC 60228 with the standard temperature coefficient applied at the insulation rating (70 °C PVC, 90 °C XLPE). Reactance simplified to 0.08 mΩ/m, the Schneider EIG cross-vendor value for typical LV cable. Adiabatic k from IEC 60364-4-43 Table 43A.

Questions engineers ask

Which standard does the sizing follow?

IEC 60364-5-52 current-carrying capacities for copper and aluminium with PVC or XLPE insulation, with the ambient-temperature and grouping correction factors from the same standard, plus a voltage-drop check against the limit you set.

What voltage-drop limit should I use?

3 % for a final circuit is the usual design value; IEC 60364-5-52 Annex G suggests 3 % for lighting and 5 % for other uses from the origin of the installation. For a UPS output feeding IT loads, many engineers tighten to 2 % so cable drop does not eat the UPS’s own regulation band.

Why does the result sometimes jump two sizes?

Two constraints are checked and the stricter one wins. A long run at high current often passes ampacity on a smaller cable but fails voltage drop, which forces the size up. The table shows every size considered so you can see which rule decided it.

Cable sizing — important limitations: This calculator checks ampacity (IEC 60364-5-52), voltage drop and — only when a fault level is entered — the adiabatic short-circuit withstand. It does NOT verify earth-fault loop impedance, protective-device coordination, neutral sizing for harmonic loads, or compliance with your local wiring code. Free-air and buried installation methods, tray spacing, soil thermal resistivity, solar exposure, and the upstream protective device are out of scope. Use this output as a starting point only; final cable specification must be verified by a qualified electrical engineer and reconciled with manufacturer datasheets, the applicable national wiring regulations (NEC, BS 7671, IEC 60364, or your local equivalent), and site-specific conditions. Power Stack accepts no liability for installation decisions made from this output.